Skip to content

AC Network Model

case.ac_model() constructs an AC network snapshot. It does not solve a power flow or include device generation and demand. No slack bus or connected network is required merely to build admittance matrices.

import numpy as np
import gridforge as gf

case = gf.load_case("case14")
ac = case.ac_model()

bus = case["bus"]
V = bus["VM"].to_numpy() * np.exp(1j * np.deg2rad(bus["VA"].to_numpy()))
Sbus_pu = V * np.conj(ac.Ybus @ V)
Sf_pu = (ac.Cf @ V) * np.conj(ac.Yf @ V)
St_pu = (ac.Ct @ V) * np.conj(ac.Yt @ V)

V is built from the current bus.VM and bus.VA values, which are not necessarily a power-flow solution. The formulas calculate network injections and branch-end flows at that voltage. Multiply complex power by case.base_mva to obtain MVA.

The returned ACModel contains:

Field Shape Meaning
bus_ids nbus IDs Real BUS_IDX values in current bus-table row order
branch_buses nbranch pairs Real from/to IDs in current branch-table row order
Cf, Ct nbranch × nbus Physical from/to bus connection matrices
Ybus nbus × nbus Complex bus admittance: Ibus = Ybus @ V
Yf, Yt nbranch × nbus Complex branch-end admittances: If = Yf @ V, It = Yt @ V
base_mva scalar Power base used to scale GS and BS

The matrices are SciPy CSR sparse matrices. Rows and columns follow current DataFrame row order, not DataFrame index labels or numeric bus-ID order. The model is an uncached snapshot; rebuild it after editing bus, branch, or base_mva.

For each online branch, GridForge uses series impedance BR_R + j*BR_X, half of the total BR_B charging at each end, and a complex tap defined by TAP and SHIFT (degrees). TAP=0 means a unit ratio. Bus shunts enter Ybus as (GS + j*BS) / base_mva; do not count these shunts again as constant-power load. These conventions match MATPOWER makeYbus.

An offline branch keeps its row and physical endpoints in Cf/Ct, but its Yf and Yt rows are zero and it contributes nothing to Ybus.