DC Model

case.dc_model() builds DC network matrices and a PTDF snapshot. It does not solve a power flow or dispatch generators.

import gridforge as gf

case = gf.load_case("case14")
dc = case.dc_model()  # Unique BUS_TYPE=3 bus is the default slack.

For case14, case.dc_model(slack_bus=2) selects bus ID 2 instead. The argument is a real BUS_IDX, not a DataFrame row position. An explicit slack can be any active bus; it need not have BUS_TYPE=3.

Calculate branch flows

Supply bus_injection_pu yourself: a balanced array of net injections in p.u., ordered as dc.bus_ids. Injection is positive; withdrawal is negative. The worked tutorial shows how to construct and balance this array from generators, demand, GS, and custom devices.

branch_flow_pu = dc.ptdf @ bus_injection_pu + dc.ptdf_flow_offset

Flow is positive from F_BUS_IDX to T_BUS_IDX. The offset is required for absolute flows with phase-shifting transformers: it is not simply branch_shift_flow, because the network also responds to phase-shift bus injections. See my blog.

Returned fields

Symbol GridForge field Shape Meaning / units
— bus_ids nbus IDs Real BUS_IDX values in current bus-table order
— branch_buses nbranch pairs Real endpoint IDs in current branch-table order
— slack_bus, base_mva scalar Chosen real BUS_IDX and MVA power base
A incidence nbranch × nbus Physical incidence: +1 at from bus, −1 at to bus
B_f Bf nbranch × nbus Maps bus angles in radians to branch flows in p.u.
B_bus Bbus nbus × nbus Maps bus angles in radians to bus injections in p.u.
H ptdf nbranch × nbus Dimensionless flow sensitivities; slack column is zero
p_f^(shift) branch_shift_flow nbranch Direct phase-shift branch-flow term, p.u.
p_bus^(shift) bus_shift_injection nbus Phase-shift bus-injection term, p.u.
p_f^(offset) ptdf_flow_offset nbranch Final fixed branch-flow term in the PTDF equation, p.u.

For an angle vector theta in radians:

bus_injection_pu = dc.Bbus @ theta + dc.bus_shift_injection
branch_flow_pu = dc.Bf @ theta + dc.branch_shift_flow

The PTDF formula above gives the same branch flows for balanced injections. For online branches, TAP=0 means a unit ratio, and SHIFT=0 means no phase shift. These settings leave the branch in service; set branch.STATUS=0 to take it out of service. SHIFT is specified in degrees. The equations and signs follow the MATPOWER makeBdc convention.

Ordering, outages and errors

  • Matrix axes follow current bus and branch row order, not pandas index labels or sorted bus IDs. GridForge does not renumber buses or drop branches.
  • An offline branch retains its row and physical endpoints in incidence, but its flow-related row and phase-shift terms are zero. Its bus references must still be valid.
  • The online network must be connected and have one slack bus. If BUS_TYPE=3 is missing or non-unique, specify slack_bus. Islands, invalid online parameters, or a singular network raise DCNetworkError.

DCModel contains dense NumPy arrays. Rebuild it after editing bus/branch data or base_mva. Editing its arrays does not modify the Case.