DC Model¶
case.dc_model() builds DC network matrices and a PTDF snapshot. It does not
solve a power flow or dispatch generators.
import gridforge as gf
case = gf.load_case("case14")
dc = case.dc_model() # Unique BUS_TYPE=3 bus is the default slack.
For case14, case.dc_model(slack_bus=2) selects bus ID 2 instead. The argument
is a real BUS_IDX, not a DataFrame row position. An explicit slack can be
any active bus; it need not have BUS_TYPE=3.
Calculate branch flows¶
Supply bus_injection_pu yourself: a balanced array of net injections in
p.u., ordered as dc.bus_ids. Injection is positive; withdrawal is
negative. The worked tutorial
shows how to construct and balance this array from generators, demand, GS,
and custom devices.
branch_flow_pu = dc.ptdf @ bus_injection_pu + dc.ptdf_flow_offset
Flow is positive from F_BUS_IDX to T_BUS_IDX. The offset is required for
absolute flows with phase-shifting transformers: it is not simply
branch_shift_flow, because the network also responds to phase-shift bus
injections. See my blog.
Returned fields¶
| Symbol | GridForge field | Shape | Meaning / units |
|---|---|---|---|
| — | bus_ids |
nbus IDs | Real BUS_IDX values in current bus-table order |
| — | branch_buses |
nbranch pairs | Real endpoint IDs in current branch-table order |
| — | slack_bus, base_mva |
scalar | Chosen real BUS_IDX and MVA power base |
A |
incidence |
nbranch × nbus | Physical incidence: +1 at from bus, −1 at to bus |
B_f |
Bf |
nbranch × nbus | Maps bus angles in radians to branch flows in p.u. |
B_bus |
Bbus |
nbus × nbus | Maps bus angles in radians to bus injections in p.u. |
H |
ptdf |
nbranch × nbus | Dimensionless flow sensitivities; slack column is zero |
p_f^(shift) |
branch_shift_flow |
nbranch | Direct phase-shift branch-flow term, p.u. |
p_bus^(shift) |
bus_shift_injection |
nbus | Phase-shift bus-injection term, p.u. |
p_f^(offset) |
ptdf_flow_offset |
nbranch | Final fixed branch-flow term in the PTDF equation, p.u. |
For an angle vector theta in radians:
bus_injection_pu = dc.Bbus @ theta + dc.bus_shift_injection
branch_flow_pu = dc.Bf @ theta + dc.branch_shift_flow
The PTDF formula above gives the same branch flows for balanced injections.
For online branches, TAP=0 means a unit ratio, and SHIFT=0 means no phase
shift. These settings leave the branch in service; set branch.STATUS=0 to
take it out of service. SHIFT is specified in degrees. The equations and
signs follow the
MATPOWER makeBdc convention.
Ordering, outages and errors¶
- Matrix axes follow current bus and branch row order, not pandas index labels or sorted bus IDs. GridForge does not renumber buses or drop branches.
- An offline branch retains its row and physical endpoints in
incidence, but its flow-related row and phase-shift terms are zero. Its bus references must still be valid. - The online network must be connected and have one slack bus. If
BUS_TYPE=3is missing or non-unique, specifyslack_bus. Islands, invalid online parameters, or a singular network raiseDCNetworkError.
DCModel contains dense NumPy arrays. Rebuild it after editing bus/branch data or base_mva. Editing its arrays does not modify the Case.